Specification parameter
Measuring medium: liquid, gas, steam, etc
Pressure form: gauge pressure, absolute pressure
Range:
0~0.6、1、2、5、10、15、20、25、30、40、50、60、100(MPa);
0~10、20、30、50、100、150、200、300、400、500、600(KPa);
-100KPa~10KPa~40MPa;
±10KPa~±100KPa;
Comprehensive accuracy: ± 0.25% FS; ± 0.5% FS; ± 1% FS
Nonlinearity: ≤ 0.5% FS
Repeatability: ≤ 0.25% FS
Output signal:
Current type: 4-20mA two-wire system; 4-20mA / 0-20mA three-wire system
Voltage type: 0 ~ 5VDC, 0 ~ 10VDC, 0.5 ~ 4.5vdc three wire system
Digital type: rs485-rtu, low power rs485-rtu
CAN2.0B (supports CANopen, J1939 Protocol)
Supply voltage:
24VDC(9~30VDC)
5VDC (0.5 ~ 4.5vdc output type)
3.1 ~ 6.1vdc (low power rs485-rtu)
Service life: ≥ 1 million times
Insulation impedance: ≥ 1000 m Ω / 100VDC
Load impedance: current output: ≤ 800 Ω; voltage output: ≥ 50K Ω
Medium temperature: - 20 ~ 150 ℃ / 250 ℃ / 350 ℃ / 500 ℃/
Ambient temperature: - 20 ~ 70 ℃
Compensation temperature: 0 ~ 70 ℃
Response time: ≤ 5ms
Overload pressure: 150% FS
Failure pressure: 3 times of measuring range (less than 40MPa); 2 times of measuring range (measuring range greater than 41mpa)
Electrical connection: Waterproof tight wire nut directly leads out, can be matched with explosion-proof electrical connection
Protection grade: IP65 / IP68
Connecting cable: hesman (din43650) / tightening nut / aviation connector, etc., standard length: 3M
Connection material: 304 / 316L
Process connection: m20x1.5, G1 / 2, ZG1 / 2, 1 / 2NPT, DN50 Specification can be made by users
UOTPUT
五、安装方式
Ordering considerations
Precautions for ordering PT500-503H products
1. Product range selection:
In order to achieve the best effect of product accuracy, life, stability and other functions, the range selection of the product is calculated by referring to the
following formula:
Range = x (1.2-1.5) times of the maximum system pressure;
The actual measuring pressure range of the product should be 15% - 80% of the range;
2. Product power supply and output:
The selection of power supply range is determined according to the output specifications of the product:
Conventional 4-20mA / 0-20mA, 0-5V / 10V output, DC 12-30vdc power supply;
General rs485-rtu output, DC 12-30vdc power supply;
0.5-4.5vdc output, DC 5VDC;
3. The user should understand the measurement medium characteristics of the product:
Medium specification, medium temperature, medium purity (whether containing impurities or particles, etc.);
4. Users should understand the installation environment and installation method of the product:
Indoor or outdoor installation;
Ambient temperature;
Required sealing level;
Vibration range of equipment;
Installation method: thread, flange, special structure;
Whether the installation space meets the overall dimension of the product;
Precautions for use
It is strictly prohibited that the power supply scope of the product exceeds the product standard;
It is forbidden to use hard objects (such as: screwdrivers, fingers, nails, etc.) to make the pressure diaphragm output by pressure measurement;
The power supply and signal lines shall be correctly connected according to the product specifications;
When the product is installed, the stress part is "process connection hexagonal wrench", and the wrench size is corresponding to the hexagonal wrench;
It is strictly prohibited that the medium temperature, pressure range and excitation voltage of the measured system exceed the rated range of the transmitter;
Pay attention to protect the outgoing cable of transmitter. When the span is too large, it is recommended to use metal tube for protection or overhead;
Pressure transmitter is a kind of precision measuring instrument. Do not force impact and fall to avoid damaging the core
The product is installed in a ventilated, dry and non corrosive environment. It is installed in the open air with protective devices to avoid direct sunlight;
Water / water leakage / soaking is strictly prohibited in the instrument of the product. Protective devices are installed in the open air to avoid direct sunlight;